WIT 20-25K-HU-GTI Series

WIT 20-25K-HU-GTI Series

WIT 20-25K-HU-GTI Series

WIT 20-25K-HU-GTI three-phase grid-tied hybrid inverter, 20 kW to 25 kW, 2 MPPT, IP66

Three-Phase Grid-Tied Hybrid Inverter · 20-25 kW

WIT 20-25K-HU-GTI Hybrid Inverter

Models: WIT 20K-HU GTI / WIT 25K-HU GTI

A three-phase grid-tied hybrid inverter series for commercial PV-plus-storage systems. Two power classes at 20 kW and 25 kW use 2 MPPT inputs with 40 A per MPPT, a 40-60 V battery port rated at 420 A, 1.1x AC load capability and IP66 protection in a high-power-density design.

20-25 kW

Rated output

2

MPPT inputs

420 A

Battery current

IP66

Protection

Product Overview

The WIT 20-25K-HU-GTI series covers 20 kW and 25 kW three-phase grid-tied hybrid models. Each model uses 2 MPPT inputs with 2 strings per MPPT, 40 A maximum current and 50 A maximum short-circuit current per MPPT. The maximum PV input voltage is 1000 V with a rated input voltage of 625 V.

The battery port accepts lithium and lead-acid batteries from 40 V to 60 V at a rated 51.2 V, with up to 420 A charge and discharge current over RS485/CAN. The AC input and output are rated at 20 kW / 22 kVA or 25 kW / 27.5 kVA with 380/400/415 V grid connection. Maximum efficiency is 97.60% and the IP66 enclosure uses air cooling.

Key Features

  • 20 A string current for high-power modules
  • 420 A maximum battery charge and discharge current
  • Low-voltage battery compatibility (40-60 V)
  • 1.1x AC load capability
  • High power density design
  • IP66 protection rating
  • 1000 V maximum PV input voltage
  • Class II DC and AC surge protection
  • RS485 / CAN / USB communication
  • WiFi / LAN monitoring available
  • OLED and LED display with APP
  • Wall-mounted installation
  • 5-year warranty

Technical Specifications

DC Input (PV)

ParameterWIT 20K-HU GTIWIT 25K-HU GTI
Maximum input power40 kW50 kW
Maximum input voltage1000 V
Start-up voltage180 V
Rated input voltage625 V
MPPT voltage range150-850 V
Number of MPPTs2
Strings per MPPT2
Maximum input current per MPPT40 A / 40 A
Maximum short-circuit current per MPPT50 A / 50 A

Battery (BAT)

Battery typeLithium battery / lead-acid battery
Rated battery voltage51.2 V
Battery voltage range40-60 V
Number of battery ports1
Maximum charge / discharge current420 A
CommunicationRS485 / CAN

AC Input (Grid)

ParameterWIT 20K-HU GTIWIT 25K-HU GTI
Rated input power20 kW25 kW
Maximum input apparent power22 kVA27.5 kVA
Rated input voltage / range380/400/415 V, -15% to +10%
AC wiring type3P3W+PE / 3P4W+PE
Maximum input current @220 V45.5 A56.8 A

AC Output (Grid)

ParameterWIT 20K-HU GTIWIT 25K-HU GTI
Rated output power20 kW25 kW
Maximum output apparent power22 kVA27.5 kVA
Maximum output current @220 V45.5 A56.8 A
Rated output voltage / range380/400/415 V, -15% to +10%
AC wiring type3P3W+PE / 3P4W+PE
Power factor adjustment range-1 to +1
THDi<3%

Efficiency

Maximum efficiency97.60%
European efficiency97.00%
MPPT efficiency99.90%

Protection

DC input reverse-polarity protectionAvailable
DC input switchAvailable
AC short-circuit protectionAvailable
AC overcurrent protectionAvailable
DC / AC surge protectionClass II / Class II
Insulation resistance monitoringAvailable
Ground fault monitoringAvailable
Residual current monitoringAvailable
Anti-islanding protectionAvailable
String monitoringAvailable
DC arc fault detectionOptional

General Data

Dimensions (W × H × D)475 × 695 × 241 mm
Weight53 kg
Operating temperature range-30 °C to +60 °C (derated above 45 °C)
Relative humidity0-95%
Maximum operating altitude4000 m
Protection ratingIP66
TopologyTransformerless
CoolingAir cooling
DisplayOLED + LED / APP
CommunicationRS485 / CAN / USB; WiFi / LAN available
InstallationWall-mounted
Warranty5 years

Applications

The series is designed for commercial three-phase grid-tied PV-plus-storage installations requiring high battery current and compact installation.

  • Commercial rooftop PV with storage
  • Backup power with low-voltage battery
  • Self-consumption optimisation
  • Peak-shaving applications
  • Demand charge reduction

OEM & Custom Requirements

Project supply and private-label requirements can be confirmed against the standard WIT 20-25K-HU-GTI platform. Share the required battery configuration and destination market.

  • Private-label enclosure and documentation
  • Power class selection from 20 kW to 25 kW
  • Battery interface configuration
  • Manual localisation for the target market
  • Packaging and delivery planning

Need a project-specific quote?

Send us the required power class, battery configuration and destination port. We will confirm the model, documentation package and delivery schedule.