Three-Phase Hybrid Inverter · 29.9-50 kW
WIT 29.9-50K-XHU Three-Phase Hybrid Inverter
Models: WIT 29.9K-XHU / WIT 30K-XHU / WIT 36K-XHU / WIT 40K-XHU / WIT 50K-XHU
A three-phase hybrid inverter platform for commercial and industrial PV with battery storage. Five power classes from 29.9 kW to 50 kW use four MPPT inputs with 40 A per MPPT and three battery ports that can be connected independently or in parallel. The series supports generator input with smart start and stop, UPS function with black start, up to three units in parallel in off-grid mode, 100% three-phase unbalanced output, 150% off-grid overload and weak grids with SCR below 1.2.
29.9-50 kW
Rated AC output
4
MPPT inputs
3
Battery ports
IP66
Protection rating
Product Overview
The WIT 29.9-50K-XHU series covers 29.9 kW, 30 kW, 36 kW, 40 kW and 50 kW three-phase hybrid models. Each model uses four MPPT inputs with two strings per MPPT, a 180-1000 V operating range, 620 V rated input voltage and 40 A maximum current per MPPT. When the battery voltage is above 800 V, the PV open-circuit voltage should stay below 850 V.
The three battery ports accept lithium and lead-acid batteries from 200 V to 900 V at a rated 512 V, with 55 A charge and discharge current per port over RS485/CAN. Generator input supports smart start and stop; diesel generator capacity should be sized at load divided by 0.7. UPS function with black start, a transfer time of 10 ms or less, 100% three-phase unbalanced output and 150% overload for 10 s cover backup and off-grid operation. Maximum efficiency is 98.10% with 97.20% Euro efficiency.
Key Features
- Four MPPT inputs with 40 A maximum current per MPPT
- Three battery ports, independent or parallel connection
- Generator input with smart start and stop
- UPS function and black start capability
- Parallel operation of up to 3 units in off-grid mode with smart load control
- 100% three-phase unbalanced output
- 150% off-grid overload capability for 10 s
- On/off-grid transfer time of 10 ms or less
- Suitable for weak grids with SCR below 1.2
- 200-900 V battery range with 55 A per port
- OLED and LED display with APP monitoring
- IP66 protection for outdoor wall-mounted installation
- 5-year standard warranty
Technical Specifications
DC Input (PV)
| Parameter | WIT 29.9K-XHU | WIT 30K-XHU | WIT 36K-XHU | WIT 40K-XHU | WIT 50K-XHU |
|---|---|---|---|---|---|
| Maximum input power | 59.8 kW | 60 kW | 72 kW | 80 kW | 100 kW |
| Maximum input voltage | 1100 V | ||||
| Start-up voltage | 195 V | ||||
| Rated input voltage | 620 V | ||||
| MPPT operating voltage range | 180-1000 V | ||||
| Number of MPPTs | 4 | ||||
| Strings per MPPT | 2 | ||||
| Maximum input current per MPPT | 40 A | ||||
| Maximum short-circuit current per MPPT | 50 A |
Battery (BAT)
| Battery type | Lithium battery / lead-acid battery |
| Rated battery voltage | 512 V |
| Battery voltage range | 200-900 V |
| Number of battery ports | 3 |
| Maximum charge / discharge current | 55 A × 3 |
| Battery communication | RS485 / CAN |
AC Input (Grid)
| Parameter | WIT 29.9K-XHU | WIT 30K-XHU | WIT 36K-XHU | WIT 40K-XHU | WIT 50K-XHU |
|---|---|---|---|---|---|
| Rated input power | 59.8 kW | 60 kW | 72 kW | 80 kW | 100 kW |
| Maximum input power | 59.8 kW | 66 kW | 79.2 kW | 88 kW | 110 kW |
| Rated input voltage / range | 380 / 400 V, -15% to +10% | ||||
| AC wiring type | 3P3W+PE / 3P4W+PE | ||||
| Rated input frequency / range | 50 Hz / 45-55 Hz, 60 Hz / 55-65 Hz | ||||
| Maximum input current | 90.6 A @220 V | 100 A @220 V | 120 A @220 V | 133.3 A @220 V | 166.7 A @220 V |
AC Input (Generator)
| Parameter | WIT 29.9K-XHU | WIT 30K-XHU | WIT 36K-XHU | WIT 40K-XHU | WIT 50K-XHU |
|---|---|---|---|---|---|
| Rated input power | 59.8 kW | 60 kW | 72 kW | 80 kW | 100 kW |
| Maximum input current (GEN / AC coupling) | 90.6 A @220 V | 100 A @220 V | 120 A @220 V | 133.3 A @220 V | 166.7 A @220 V |
| Rated input voltage | 380 / 400 V | ||||
| Wiring type | 3P3W+PE / 3P4W+PE | ||||
| Rated input frequency | 50 Hz / 60 Hz |
AC Output (Grid)
| Parameter | WIT 29.9K-XHU | WIT 30K-XHU | WIT 36K-XHU | WIT 40K-XHU | WIT 50K-XHU |
|---|---|---|---|---|---|
| Rated output power | 29.9 kW | 30 kW | 36 kW | 40 kW | 50 kW |
| Maximum output apparent power | 29.9 kVA | 33 kVA | 39.6 kVA | 44 kVA | 55 kVA |
| Maximum output current | 45.3 A @220 V | 50 A @220 V | 60 A @220 V | 66.7 A @220 V | 83.3 A @220 V |
| Rated output voltage / range | 380 / 400 V, -15% to +10% | ||||
| AC wiring type | 3P3W+PE / 3P4W+PE | ||||
| Rated grid frequency / range | 50 Hz / 45-55 Hz, 60 Hz / 55-65 Hz | ||||
| Power factor adjustment range | -1 to +1 | ||||
| THDi | <3% |
AC Output (Back-up Load)
| Parameter | WIT 29.9K-XHU | WIT 30K-XHU | WIT 36K-XHU | WIT 40K-XHU | WIT 50K-XHU |
|---|---|---|---|---|---|
| Rated output power | 29.9 kW | 30 kW | 36 kW | 40 kW | 50 kW |
| Maximum output apparent power | 29.9 kVA | 45 kVA | 54 kVA | 60 kVA | 75 kVA |
| Maximum output current | 68.0 A | 68.2 A | 81.8 A | 90.9 A | 113.6 A |
| Rated output voltage | 220 / 230 V (L-N), 380 / 400 V (L-L) | ||||
| Rated output frequency | 50 Hz / 60 Hz | ||||
| THDv | <3% (linear full load) | ||||
| Load unbalance | 100% three-phase unbalance | ||||
| Overload capability | 150% for 10 s | ||||
| On/off-grid transfer time | ≤10 ms |
Efficiency
| Maximum efficiency | 98.10% |
| Euro efficiency | 97.20% |
Protection
| DC input reverse-polarity protection | Available |
| DC input switch | Available |
| AC short-circuit protection | Available |
| AC overcurrent protection | Available |
| DC / AC surge protection | Class II / Class II |
| Insulation resistance monitoring | Available |
| Ground fault monitoring | Available |
| Residual current monitoring | Available |
| Anti-islanding protection | Available |
| String monitoring | Available |
| Anti-PID function | Optional |
| DC arc fault detection | Optional |
General Data
| Dimensions (W × H × D) | 920 × 585 × 320 mm |
| Weight | 92 kg |
| Operating temperature range | -30 °C to +60 °C (derated above 50 °C) |
| Relative humidity | 0-95% |
| Maximum operating altitude | 4000 m |
| Protection rating | IP66 |
| Topology | Transformerless |
| Cooling | Air cooling |
| Display | OLED + LED / APP |
| Communication | RS485 / CAN / USB available; WiFi / LAN available |
| Installation | Wall-mounted |
| Warranty | 5 years |
| Certification | IEC/EN 61000-6-1, IEC/EN 61000-6-3, IEC/EN 62109-1, IEC/EN 62109-2, IEC/EN 62477-1, NRS 097-2-1:2017, EN 50549-1, NC RFG, PSE-2018, TPIREE-2021, IEC 62116, IEC 61727, G99:2020, VDE 4105 |
Applications
The series is intended for commercial and industrial PV systems that combine battery storage, backup loads and generator support, including weak-grid sites.
- Commercial and industrial rooftop PV with storage
- Backup power for critical loads
- Off-grid and weak-grid micro-grid systems
- Generator-hybrid sites with smart start and stop
- Sites needing three independent battery channels
OEM & Custom Requirements
Project supply and private-label requirements can be confirmed against the standard WIT 29.9-50K-XHU platform. Share the required power class, battery configuration, generator plan and destination market.
- Private-label enclosure and documentation
- Power class selection from 29.9 kW to 50 kW
- Battery and generator interface configuration
- Manual localisation for the target market
- Packaging and delivery planning
Need a project-specific quote?
Send us the required power class, battery configuration, generator plan and destination port. We will confirm the model, documentation package and delivery schedule.